  产品名称:测量站 OVAL D系列
发布时间:2024-3-28 9:42:2

产品图片
  • 测量站 OVAL D系列
产品简介
   

Model OVAL D
Introduction

OVAL D measuring station is designed and developed to monitor oil flow rates measured by model SR -oval gear meters in circulation lubrication systems.

The OVAL D measuring station(s) can be as an independent station(s), connected to Kytola KVMWIN control room software or to customers DCS / PLC via Modbus RTU protocol.

OVAL D measuring station
                                    

             Features

  • Stainless steel housing 
  • Local display
  • Serial interface RS485 or RS422
  • Communication with upper level systems
  • Modbus RTU protocol
  • Kytola KVM protocol
  • Alarm relays
  • Alarm inhibits
  • Alarm groups

             Typical applications

  • Lubrication oil monitoring
  • Industrial oil flow monitoring
  • Process control

 

 

 

 

 

 

 

 

Technical data

Housing

Stainless steel, IP65

Supply voltage

24 VDC / 0,6 A or 110 - 240 VAC / 50 - 60 Hz

Display

4 x 20 characters + 4 pcs buttons

Communication

Modbus RTU (RS485 / RS422) or Kytola KVM (RS422) protocol 

Measuring points / station

Max. 48 points with Modbus RTU protocol (96 points on special request) or max. 48 points with Kytola KVM protocol

Max. number of stations

Up to 64 stations can be connected to one serial bus

Alarm relays

3 pcs potential-free relays for Hi flow, Lo flow and LoLo flow alarms + 1 pc programmable relay

Alarm inhibition inputs

3 pcs optoisolated inputs to prevent alarms

Sensor types

Kytola coil- or NAMUR-sensor; DIN 19234 




 


 

 
 